1

Medium

Why is ammonia (NH₃) considered a toxic refrigerant?


It is flammable and can form explosive mixtures with air
It is highly irritating to the respiratory tract and toxic if inhaled
It is colourless and odourless, so it is difficult to detect
It does not react with water, which makes it difficult to neutralise

2

Difficult

What is the main difference between a dry evaporator and a flooded evaporator?


A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas
A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator
A dry evaporator does not require an expansion valve, whereas a flooded one does
A dry evaporator has a lower operating pressure than a flooded one

3

Difficult

What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?


Positive pressure, in the range of 5–10 bar
Negative pressure (vacuum), below 0 bar
A pressure varying between 10 and 20 bar
Atmospheric pressure, approximately 1 bar

4

Difficult

Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?


They are persistent, accumulate in the environment and may be toxic
They cause rapid cooling of the atmosphere
They are readily biodegradable, so they only pollute the environment for a short time
They are climate-neutral

5

Difficult

What is the basic requirement when charging a system with R717 (NH₃)?


Charging must only take place at temperatures below 0°C
Charging should take place in a well-ventilated area using appropriate personal protective equipment
Charging can be carried out without personal protective equipment
NH₃ can be charged together with air

6

Difficult

How should oil be handled in systems using R717?


The oil does not require any monitoring
Oil can be mixed with any refrigerant
The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks
Oil has no effect on the system’s operation

7

Difficult

What is the correct procedure for recovering R717 from a system?


The refrigerant can be drained into the sewer system
The gas can be released into the atmosphere
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
Recovery is not required

8

Difficult

How should R717 (NH₃) be stored?


In unmarked plastic containers
Near heat sources
In sealed, labelled containers, in a cool and well-ventilated place
In any open containers

9

Difficult

What should be done in the event of R717 contamination?


Release into the atmosphere
The refrigerant must be purified or sent for disposal in accordance with regulations
Add water to dilute it
Continue to use without restriction

10

Difficult

What is the main hazard associated with an R717 leak during maintenance work?


Damage to electrical equipment only
No risk whatsoever
Increased cooling efficiency
Toxic to humans and may cause chemical burns

11

Difficult

What action should be taken if an NH₃ leak is detected?


Close your eyes and carry on working
Ignore it and carry on working
Increase the pressure in the system
Evacuate personnel immediately and remove the source of the leak, if it is safe to do so

12

Difficult

What role do scrubbers play in NH₃ systems?


They are used to measure temperature
They store the refrigerant
Neutralises ammonia through absorption in a liquid (e.g. water)
They increase the pressure in the system

13

Difficult

How should the system be prepared before filling with R717?


There is no need to check it
The pressure must be increased above the standard level
Simply start it up
Check for leaks, remove air and moisture, and create a vacuum

14

Difficult

What are the transport requirements for R717?


It can be transported in open containers
Transport is not subject to regulations
It can be transported without labelling
Must be transported in suitable, labelled containers in accordance with ADR regulations

15

Difficult

What personal protective equipment is required when working with NH₃?


Workwear only
No requirements
Safety goggles, gloves and respiratory protective equipment
Only a safety helmet

16

Difficult

Which statement best describes the behaviour of R717 and mineral compressor oil?


In an R717 system, a return oil line cannot be used because the oil is too hot
R717 mixes very well with compressor oil and easily returns to the compressor
R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717
R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717

17

Difficult

Which system may require manual oil recovery?


Secondary system using R744
An R717 system
Supercritical ‘booster’ system using R744
R744 cascade system

18

Difficult

Which refrigerant is lighter than air?


R717
R1234ze
R744
R1270

19

Difficult

R717 is highly corrosive to


titanium
stainless steel
copper
aluminium

20

Difficult

What is the effect of repeatedly opening the relief valve?


The relief pressure rises
The valve remains fully open continuously
The valve will not open
The relief pressure drops

21

Difficult

What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?


P2 = (P1 × T2)/T1
P2 = T1/(P1 × T2)
P2 = (P1 × T1)/T2
P2 = T2/(P1 × T1)

22

Difficult

What is the recommended alarm level for fixed leak detection systems for R717?


500,000 ppm
50,000 ppm
500 ppm
5,000 ppm

23

Difficult

Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?


Because NH₃ reacts with the motor windings and hermetic compressors are not used
To reduce the condensing pressure
To increase the amount of refrigerant in the system
Because compressors with a separate motor are cheaper

24

Difficult

Which type of compressor is most commonly used in large ammonia systems?


Rotary vane compressor
Diaphragm compressor
A reciprocating or screw compressor
Hermetic scroll

25

Difficult

How is the capacity of a piston compressor regulated in NH₃ systems?


Solely by adjusting the oil volume
By unloading the cylinders or changing the rotational speed
By reducing the refrigerant charge
By increasing the condensing pressure

26

Difficult

How is the capacity of a screw compressor most commonly controlled?


By adjusting the oil level
By using a slide valve
By closing the suction valve
By changing the type of oil

27

Difficult

When is two-stage compression used in NH₃ systems?


At small temperature differences
Exclusively in small systems
At very low vapour pressures and high pressure differentials
Only with water-cooled condensers

28

Difficult

What is the advantage of two-stage compression over single-stage compression?


Higher energy consumption
Higher efficiency and lower discharge temperature
No need for a separator
Lower efficiency

29

Difficult

How does an evaporative condenser used in NH₃ systems work?


It does not require a water supply
It utilises the evaporation of water to increase cooling efficiency
It transfers heat only to the air
Operates without a fan

30

Difficult

What is the function of the liquid separator in an NH₃ system?


Regulates the condensing pressure
It prevents liquid from entering the compressor
Increases the discharge temperature
It separates oil from the refrigerant

31

Difficult

What is the purpose of monitoring the liquid level in the separator?


To reduce the condensing temperature
To control the condenser fan
To maintain the correct refrigerant level and prevent the compressor from flooding
To increase the oil volume

32

Difficult

What is the role of the float switch in NH₃ systems?


It controls the fan’s operation
It regulates the condensation temperature
It monitors the liquid level in the tank or separator
It is used to detect leaks

33

Difficult

What is a thermosiphon in NH₃ systems?


A defrosting device
A type of evaporator
A type of safety valve
An oil circulation system utilising differences in pressure and temperature

34

Difficult

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


To reduce the pressure
To increase the amount of refrigerant
Because the oil mixes only with water
Because NH₃ does not mix with most compressor oils

35

Difficult

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To separate the oil from the refrigerant and return the oil to the compressor
To increase fan efficiency
To lower the condensation temperature

36

Difficult

Which NH₃ system features direct evaporation of the refrigerant in the evaporator?


Glycol system
Direct expansion (DX) system
Thermosiphon system
Indirect system

37

Difficult

What is the characteristic feature of a flooded evaporator system?


No level control is required
The evaporator is filled exclusively with vapour
The evaporator contains a large amount of liquid, which improves heat transfer
No separator is used

38

Difficult

What is the main difference between a direct and an indirect system?


In an indirect system, no compressor is used
In an indirect system, NH₃ flows directly into the space being cooled
In a direct system, there is no evaporator
In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load