F-Gas English Low GWP

All questions
HFC | Flammable | CO₂ | NH₃
Easy questions | Medium questions | Difficult questions

1

Medium

What is R1270?


Propane
n-Butane
Isobutane
Propene (propylene)

2

Medium

What is the main design difference in hydrocarbon refrigeration systems?


No need for safety measures
The need to eliminate ignition sources and limit the charge because of the refrigerant's flammability
Lower energy efficiency
Higher operating pressures

3

Medium

How do compressors used in hydrocarbon systems differ?


There is no difference
They must be approved by the manufacturer for the specific flammable refrigerant (e.g. electrical components that are not ignition sources, suitable oil)
They must operate at higher pressures than HFC compressors
They need no lubrication

4

Medium

What distinguishes class 2L refrigerants from class 2?


No lower flammability limit
Higher toxicity
Heat of combustion above 19 MJ/kg
A maximum burning velocity of no more than 10 cm/s

5

Medium

What is the lower flammability limit (LFL) of propane R290?


Approx. 0.38 kg/m³
Approx. 1.8 kg/m³
Approx. 0.307 kg/m³
Approx. 0.038 kg/m³ (approx. 2.1% by volume)

6

Medium

Equipment marked 'Ex II 3G' may be used in zone:


0
20 (dusts)
1
2 (explosive gas atmosphere unlikely and short-lived)

7

Medium

How is explosion hazard zone 2 defined?


An explosive atmosphere is present continuously or for long periods
An explosive atmosphere is likely to occur in normal operation
An area where flammable refrigerants are never used
An explosive atmosphere is not likely in normal operation and, if it occurs, persists only for a short period

8

Medium

Under which UN number is propane (R290) carried under ADR?


UN 1978
UN 3252
UN 1005
UN 3337

9

Medium

At what concentration should a portable flammable gas detector used for R290 work raise an alarm at the latest?


At 150% of LFL
At 100% of LFL
At 5% propane by volume
No higher than 25% of LFL

10

Medium

How should a recovery cylinder be prepared before filling it with a hydrocarbon refrigerant?


Evacuate it (no air) and label it for the specific flammable refrigerant
Partly fill it with nitrogen to 5 bar
No preparation is needed
Purge it with compressed air

11

Medium

What is the correct approach in a risk analysis before work on an HC system?


First eliminate hazard sources (e.g. ignition sources); where this is not possible, identify them and apply mitigating measures (ventilation, detection, PPE)
First select PPE, then possibly remove ignition sources
Having a fire extinguisher is sufficient
The risk analysis is done after the work is finished

12

Medium

Why must the charge of small, critically charged R290 systems be weighed to within a few grams during service?


Because R290 is more expensive than HFCs
Because extra R290 improves efficiency
Because scales are not needed – charging is done by sight glass
Small charge deviations significantly change superheat/subcooling and efficiency, and overcharge increases the risk in a leak